Permit Number: T13CM04856
Parcel: 11710020G

Address:
369 N MEYER AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T13CM04856
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/23/2013 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS
Date: 12-23-13
Activity: T13CM04856
Address: 369 N Meyer Av
Applicant: Tim Polito

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Residential Code with local amendments. In order to facilitate a shorter back check time, we request that you please provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

PREVIOUS COMMENTS:
"...fire rating construction...all projections that fall within 2' to 3' of property line, R302."
Specify fire rated overhang at porch enclosure or indicate that the overhang will not extend into the 36" fire separation area adjoining the property line.

"...show how GLB...is connected to existing adobe wall."
Structural calculation sheets 5-9 do not indicate connection of floor system to existing adobe wall. Previously approved drawings request field verification of wall condition. Specify connection and support of proposed floor system to existing adobe walls.

"Electrical sub-panel may not be located in attic storage."
The subpanel has been relocated to another area previously designated as storage and now designated as a mechanical room. Verify the minimum working clearance available in front of the proposed electrical panel location meets the minimum 6.5 foot clear height required by E3405.2.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/27/2013 CPIERCE1 REJECT SHELF Completed