Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T13CM04840
Review Name: OTHER
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/09/2013 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
09/09/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
09/09/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The literature from Amtrol did not call for the installation of a shutoff valve between the expansion tank and the water heater and their installation drawings also showed no valves. Remove the shut off valve(s) located between the expansion tank and the water heater. [Initial comment: Provide information to show that the installation of the thermal expansion tank with a shut-off valve located between the expansion tank and the water heater complies with the manufacturer's listing requirements. Reference: Section 303.2, IPC 2012.] |
09/11/2013 | FRODRIG2 | BUILDING-COMMERCIAL | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/11/2013 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |