Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T13CM04840
Parcel: 132130730

Review Status: Completed

Review Details: OTHER

Permit Number - T13CM04840
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/09/2013 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
09/09/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
09/09/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The literature from Amtrol did not call for the installation of a shutoff valve between the expansion tank and the water heater and their installation drawings also showed no valves. Remove the shut off valve(s) located between the expansion tank and the water heater. [Initial comment: Provide information to show that the installation of the thermal expansion tank with a shut-off valve located between the expansion tank and the water heater complies with the manufacturer's listing requirements. Reference: Section 303.2, IPC 2012.]
09/11/2013 FRODRIG2 BUILDING-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/11/2013 FERNE RODRIGUEZ OUT TO CUSTOMER Completed