Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T13CM04840
Parcel: 132130730

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM04840
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/13/2013 KEN BROUILLETTE FIRE REVIEW Denied PLEASE UPDATE PLANS TO CURRENT ADOPTED CODES
08/14/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The International Plumbing Code, 2012, is the controlling code for this activity, not the 2009 International Plumbing Code. Reference: Section 101, IBC 2012.
2. Provide information to show that the installation of the thermal expansion tank with a shut-off valve located between the expansion tank and the water heater complies with the manufacturer's listing requirements. Reference: Section 303.2, IPC 2012.
3. Provide the third-party listing information for the specified shampoo sinks. Reference: Section 303.4, IPC 2012.
4. Provide tempered water for the lavatory using an approved device conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.
5. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves (e.g. clothes washer). Reference: Section 604.9, IPC 2012.
6. If the specified shampoo sink is equipped with a sprayer, provide an approved method of backflow protection for the sprayer. Reference: Sections 608.1 and 608.15.4.1, IPC 2012.
08/14/2013 ROBERT SHERRY WATER REVIEW Approved
08/14/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The 2012 International Mechanical Code with Local Amendments is the relevant code for this activity.
2. Show how adequate outside air is to be provided to the room so that the air pressure in the suite remains essentially neutral. Reference: Section 501.4, IMC 2012.
3. Provide signage indicating the total equivalent length of the concealed dryer exhaust duct. Reference: Section 504.6.5, IMC 2012.
4. Detail 1/M1 indicates that the existing heat pump unit is equipped with an economizer. Clarify how excess outside air relief from the building is to be accomplished. Reference: Section C403.3.1.1.4, IECC 2012.
08/20/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM04840
1570 E Tucson Marketplace
TI Great Clips

1. Provide 2012 IECC Budget Lighting Calculations, Com Ck
ok, required for TI sumittals per City.
2. The service is tied into an existing 1200 amp service, TI per submittal requirements you must provide an existing load and include the load for this space for a current total.

Both requirements per City of Tucson TI Submittal Requirements PDSD, Tucson.


Ray T Majuta
Elect Plan Review
PDSD, Tucson
8/21/2013
Ray.Majuta@tucsonaz.gov
08/28/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A1; APPLICABLE CODES: REVISE THE CODES (ALL HAVE AMENDMENTS) TO THE 2012 IBC, IPC, IMC, IECC, AND IFC; 2011 NEC; 2012 IFGC; 2009 ICC/ANSI A117.1; REMOVE THE ADAAG.
2. SHEET A1; TOILET HEIGHTS: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE DIMENSIONS.
3. SHEET A1; TOILET HEIGHTS: LOCATE THE VERTICAL GRAB BAR FROM THE BACK WALL PER THE ICC/ANSI FIGURE 604.5.1.
4. SHEET A3; WALL FINISH PLAN: THE IBC SECTIONS 1210.2.1 AND 1210.2.2 HAVE REQUIREMENTS FOR FLOOR, WALL, AND PARTITION CONSTRUCTION ELEMENTS AND FINISH MATERIALS THAT WERE NOT INDICATED ON THESE PLANS. PROVIDE.
5. SHEET A4; EXISTING DEMISING WALL: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE NOTES.
6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/09/2013 AROMERO4 OUT TO CUSTOMER Completed
09/09/2013 CPIERCE1 REJECT SHELF Completed