Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM04840
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/13/2013 | KEN BROUILLETTE | FIRE | REVIEW | Denied | PLEASE UPDATE PLANS TO CURRENT ADOPTED CODES |
08/14/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The International Plumbing Code, 2012, is the controlling code for this activity, not the 2009 International Plumbing Code. Reference: Section 101, IBC 2012. 2. Provide information to show that the installation of the thermal expansion tank with a shut-off valve located between the expansion tank and the water heater complies with the manufacturer's listing requirements. Reference: Section 303.2, IPC 2012. 3. Provide the third-party listing information for the specified shampoo sinks. Reference: Section 303.4, IPC 2012. 4. Provide tempered water for the lavatory using an approved device conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012. 5. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves (e.g. clothes washer). Reference: Section 604.9, IPC 2012. 6. If the specified shampoo sink is equipped with a sprayer, provide an approved method of backflow protection for the sprayer. Reference: Sections 608.1 and 608.15.4.1, IPC 2012. |
08/14/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
08/14/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. The 2012 International Mechanical Code with Local Amendments is the relevant code for this activity. 2. Show how adequate outside air is to be provided to the room so that the air pressure in the suite remains essentially neutral. Reference: Section 501.4, IMC 2012. 3. Provide signage indicating the total equivalent length of the concealed dryer exhaust duct. Reference: Section 504.6.5, IMC 2012. 4. Detail 1/M1 indicates that the existing heat pump unit is equipped with an economizer. Clarify how excess outside air relief from the building is to be accomplished. Reference: Section C403.3.1.1.4, IECC 2012. |
08/20/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T13CM04840 1570 E Tucson Marketplace TI Great Clips 1. Provide 2012 IECC Budget Lighting Calculations, Com Ck ok, required for TI sumittals per City. 2. The service is tied into an existing 1200 amp service, TI per submittal requirements you must provide an existing load and include the load for this space for a current total. Both requirements per City of Tucson TI Submittal Requirements PDSD, Tucson. Ray T Majuta Elect Plan Review PDSD, Tucson 8/21/2013 Ray.Majuta@tucsonaz.gov |
08/28/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A1; APPLICABLE CODES: REVISE THE CODES (ALL HAVE AMENDMENTS) TO THE 2012 IBC, IPC, IMC, IECC, AND IFC; 2011 NEC; 2012 IFGC; 2009 ICC/ANSI A117.1; REMOVE THE ADAAG. 2. SHEET A1; TOILET HEIGHTS: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE DIMENSIONS. 3. SHEET A1; TOILET HEIGHTS: LOCATE THE VERTICAL GRAB BAR FROM THE BACK WALL PER THE ICC/ANSI FIGURE 604.5.1. 4. SHEET A3; WALL FINISH PLAN: THE IBC SECTIONS 1210.2.1 AND 1210.2.2 HAVE REQUIREMENTS FOR FLOOR, WALL, AND PARTITION CONSTRUCTION ELEMENTS AND FINISH MATERIALS THAT WERE NOT INDICATED ON THESE PLANS. PROVIDE. 5. SHEET A4; EXISTING DEMISING WALL: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE NOTES. 6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/09/2013 | AROMERO4 | OUT TO CUSTOMER | Completed |
09/09/2013 | CPIERCE1 | REJECT SHELF | Completed |