Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM04813
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/07/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Needs Valuation 2. Provide detail of typical interior wall partition showing compliance with 2012 IBC, Section 1607.14, laterial loading minimum of 5 psf. |
| 08/07/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the ventilation calculations to include ventilation for the corridor, storage room, and the server room. |
| 08/07/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/07/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/07/2013 | RONALD BROWN | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 08/07/2013 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 08/07/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Revise the information in the gas demand table to correlate with the developed lengths shown on MP1.0. |
| 08/08/2013 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 08/08/2013 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 08/12/2013 | CPIERCE1 | WWM | REVIEW | Needs Review |