Permit Number: T13CM04795
Parcel: 13322500E

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM04795
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/07/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008).
2. Provide tempered water for the lavatories using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.
3. Provide a cleanout for the horizontal drain serving the mop sink and the break room sink, SK-1; the cleanout shall be sized per Section 708.7, IPC 2012. Reference: Sections 708.3.1, IPC 2012.
4. Clarify which venting method is being used for protecting the trap of the mop sink. Reference: section 901.2.1, IPC 2012.
08/07/2013 ROBERT SHERRY WATER REVIEW Denied Provide the size of the water meter and the reduced pressure backflow prevention assembly at the water meter; show their location.
08/07/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008).
2. Provide information on the sequence of operation for the exhaust fan serving the restrooms to show that all of the air supplied to the restrooms will be exhausted. The exhausted air from the restrooms shall be limited to no more than 10% of any subsequent supply air stream. Reference: Section 403.2.1 (4), IMC 2012.
3. Provide justification for the use of a Zone Air Distribution Effectiveness (Ev) of 1.0 for a ceiling supply, ceiling return system using a gas-fired rooftop units. Reference: Section 403.3.1.2, IMC 2012.
4. Revise the mechanical design as required to avoid using corridor 109 as a return air duct. Reference: Section 601.2, IMC 2012.
5. All new work (e.g. insulation for new ducts) shall at least comply with the requirements of the current energy code, not necessarily just "match existing". Reference: Section 101.4.3, IECC 2012.
08/08/2013 MARTIN BROWN FIRE REVIEW Approved
08/09/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM04795
7125 E Broadway Bl
Floor & Decor T I Retail

1. Sheet E001 indicates 2005 NEC, change to comply with 2011 NEC on electrical plans.
2. Regarding Mech Plans Examiner comments, the ex-fan
for restrooms to come on when air supplied by AC unit. Electrical note on Sheet E401 does say to coordinate with HVAC contractor. Will need to see this accomplished on plan. May be provided by HVAC contractor.
3. Sheet E601, verify size of service.
4. Why is new Panel LB1 fed with 4 3/0's & #4 G when the panel is only 100 amp bus rated ?

Ray T Majuta
Elect Plan Review
PDSD, City of Tucson
8/9/2013
Ray.Majuta@tucsonaz.gov
08/12/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied SHEET LS100
1. Delete the Flordia Building Code 2009 and all the code analysis completed using this code reference
2. Provide a complete and accurate code analysis using the 2012 IBC and all other City of Tucson adopted codes listed on our web site and on sheet SP-1.
SHEET A700
3. Please provide structural analysis of partition types 1, 2, 3 and 4 showing compliance with the 2012 IBC, Section 1607.14; 5 psf lateral load.
STRUCTURAL
4. Provide structural calculations for:
a. all structural modifications shown on sheets S0.1 and S01.1.
b. The wall mounted water heater including structural detailing and wall load analysis.
5. Please provide certification of special inspectors required for special inspections as per 2012 IBC, Chapter 17.
END OF REVIEW

Final Status

Task End Date Reviewer's Name Type of Review Description
08/21/2013 CPIERCE1 REJECT SHELF Completed