Permit Number: T13CM04787
Parcel: 11306045A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM04787
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/06/2013 KEN BROUILLETTE FIRE REVIEW Approved
08/06/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the mechanical design as required to avoid using the corridor as a return air duct (non-residential occupanies over 1,000 square feet are not exempt from this requirement). Reference: Section 601.2, IMC 2012.
08/06/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
08/06/2013 ROBERT SHERRY WATER REVIEW Approved
08/06/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/06/2013 JASON GREEN ENGINEERING REVIEW Approved
08/06/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide a sealed copy of sheet P.1
08/06/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/07/2013 TERRY STEVENS ZONING REVIEW Approved
08/08/2013 AROMERO4 WWM REVIEW Needs Review