Permit Review Detail
Review Status: Completed
Review Details: WALK THRU - COMM
Permit Number - T13CM04737
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/17/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Coordinate the structural design (sketch included with the calculations) with detail 2/A-1. [Second comment: Comment not addressed.] [Initial comment: Provide the installed weight of the proposed Type I hood and provide structural calculations and details to show that the Type I hood is supported from the building structure in accordance with Section 507.6, IMC 2006. Reference: Section 302.1, IMC 2012.] |
09/17/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The drawings still show vents running horizontally below the finished floor (4 individual vents plus a common vent are located below the finished floor). [Second comment: The 2" vent below the finished floor does not appear to be 6" above the flood rim of the mop sink.] [Initial comment: Verify that all of the vents rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2012.] |