Permit Review Detail
Review Status: Completed
Review Details: WALK THRU - COMM
Permit Number - T13CM04737
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/03/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
09/03/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
09/03/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. Provide listing information for the proposed reduced pressure backflow preventer (Watts N-9). Reference: Section 608.1, IMC 2012. 2. The 2" vent below the finished floor does not appear to be 6" above the flood rim of the mop sink. [Initial comment: Verify that all of the vents rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2012.] |
09/03/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Section C403.2.4.3.3 requires that the controls have an automatic start capability. [Initial comment: Show that the proposed HVAC system meets the control requirements of Sections C403.2 and C403.3. Reference: Section C303.1, International Energy Conservation Code 2012.] 2. Comment not addressed. [Initial comment: Provide the installed weight of the proposed Type I hood and provide structural calculations and details to show that the Type I hood is supported from the building structure in accordance with Section 507.6, IMC 2006. Reference: Section 302.1, IMC 2012.] 3. Comment not addressed. [Initial comment: Unless the proposed Type I hood has been factory-built and tested in accordance with UL 710, the minimum air flow rates shall conform to the requirements of Section 507.13, IMC 2012 for a medium-duty appliance. Reference: Section 507.1, IMC 2012.] 4. Comment not addressed. [Initial comment: Show that the operation of the proposed Type I hood complies with the requirements of Section 507.2.1.1, IMC 2012.] |
09/03/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approv-Cond | SEPARATE PERMIT REQUIRED FOR HOOD SUPPRESSION SYSTEM PROPOSED. IT SHALL BE CONNECTED TO THE BUILDINGS FIRE ALARM SYSTEM. |
09/17/2013 | FRODRIG2 | WWM | REVIEW | Completed |