Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM04731
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/02/2013 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 08/02/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide controls for the ductless heat pump that meet the requirements of Section C403.2.4.1, IECC 2012. |
| 08/02/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1. Cannot locate circuit A 2,4 on power plan. Ray Majuta DSD, Tucson 8/02/2013 |
| 08/02/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/02/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. As per 2012 IBC, Section 2902.2, 2 toilet rooms are required. 2. Provide structural calculations for: a. All new roof top mounted HVAC equip b. Wall mounted water heater END OF REVIEW |
| 08/02/2013 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 08/02/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The tailpiece for a lavatory is 1-1/4", not 2". 2. Show how the cold water piping for the evaporative coolers is to be protected from freezing |
| 08/02/2013 | RONALD BROWN | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | |
| 08/05/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 08/12/2013 | SPOWELL1 | WWM | REVIEW | Needs Review |