Permit Number: T13CM04731
Parcel: 10309068D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM04731
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2013 DAVID RIVERA ZONING REVIEW Approved
08/02/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide controls for the ductless heat pump that meet the requirements of Section C403.2.4.1, IECC 2012.
08/02/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied 1. Cannot locate circuit A 2,4 on power plan.

Ray Majuta
DSD, Tucson
8/02/2013
08/02/2013 ROBERT SHERRY WATER REVIEW Approved
08/02/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. As per 2012 IBC, Section 2902.2, 2 toilet rooms are required.
2. Provide structural calculations for:
a. All new roof top mounted HVAC equip
b. Wall mounted water heater
END OF REVIEW
08/02/2013 LOREN MAKUS ENGINEERING REVIEW Approved
08/02/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The tailpiece for a lavatory is 1-1/4", not 2".
2. Show how the cold water piping for the evaporative coolers is to be protected from freezing
08/02/2013 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
08/05/2013 KEN BROUILLETTE FIRE REVIEW Approved
08/12/2013 SPOWELL1 WWM REVIEW Needs Review