Permit Number: T13CM04719
Parcel: 12109290B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T13CM04719
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/21/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The exterior wall descriptions (sheet 1.1.1) call for continuous R-5 insulation but no cavity insulation; the COMcheck component description shows R-4 continuous insulation and R-18 cavity insulation. The window notes (sheet 8.1) do not include the U-factor or the solar heat gain coefficient for the windows. [Initial comment: Provide energy code compliance calculations for the building envelope, the mechanical systems, and the interior lighting; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections C103.2 and C401.2, International Energy Conservation Code 2012.]
10/21/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide the registrant's seal on sheet P1.6. [Initial comment: Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.]
2. Revise the size of the natural gas pipe located between the branch serving DOA-1 and the branch serving AC-1 in detail 3/P1.4. [Initial comment: Revise the size of the natural gas pipe located between the branch serving DOA-1 and the branch serving AC-1. Reference: Section 402.4, IFGC 2012.]
10/22/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM04719
2221 N Rosemont

Last review sheet dated 8/26/2013, requested 2012 IECC Lighting Compliance Report. Letter from Enrique Giron indicates one has been provided, could not find one submitted with plans ?

Ray T Majuta
Electrical Plan Review
PDSD, Tucson
10/22/2013
520/837/4988
Ray.Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
10/24/2013 CPIERCE1 REJECT SHELF Completed