Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T13CM04719
Parcel: 12109290B

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T13CM04719
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/09/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. Show the size of the pipe serving the proposed gas-fired appliances, DOA-2. Reference: Section 402.1, IFGC 2012.
3. Revise the size of the natural gas pipe located between the branch serving DOA-1 and the branch serving AC-1. Reference: Section 402.4, IFGC 2012.
4. Revise the total gas load shown in detail 3/P1.4.
5. Clearly identify the hot water return lines (currently called out as "HW").
6. Hot water recirculation is not optional, delete the note on detail 201/P2.0 that implies that a hot water return is optional. Reference: Section 607.2, IPC 2012.
08/09/2013 ROBERT SHERRY WATER REVIEW Approved
08/12/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify the presence of door grilles in corridors protected by fire-smoke dampers (e.g. rooms 107, 118, 119, 202, 203, 205, and 208). Reference: Section 407.3.1, IBC 2012.
2. Provide energy code compliance calculations for the building envelope, the mechanical systems, and the interior lighting; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections C103.2 and C401.2, International Energy Conservation Code 2012.
3. This building is classified as an I-2 occupancy which is commercial, not residential. Revise the control notes for the HVAC equipment to reflect requirements found in the commercial provisions of the 2012 IECC.
4. Revise the design of supply fans SF-1, SF-2, and SF-3 per the manufacturer's installation instructions (see sheet M1.7 and detail 121/M2.2). Reference: Section 304.1, IMC 2012.
08/15/2013 MARTIN BROWN FIRE REVIEW Denied on sheet 0.2. Fix panic hardware note indicating that it is not required.. Please add 2012 IFC as a code used for review.
Is section 1008.1.9.6 of the IFC or IBC, being used for exiting?
08/20/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied GENERAL
1. Please provide a floor plan with all door and window schedule identification numbers.
SHEET 0.2
2. Provide panic hardware as required by the 2012 IBC, Section 1008.1.10 for all assembly areas with 50 or more occupants. Please confirm loads for rooms 100, 123, 231, and 209 as per Table 1004.1.2 and indicate on plans.
3. There are several doors that do not appear to meet the minimum accessible clearances as required by ICC A117.1, Section 404.2.3.2. These doors can not be identified because there are no identification numbers on the plans. Please reference comment 1.
SHEET 1.2
4. Detail E does not work.
a. Top cap flashing is shown wrapped around the bottom of an extended parapet wall and tucked neatly into a surface mounted 2 piece flashing. The elevations show that there is no parapet wall above these scuppers. Please reconcile.
b. Bottom of leader box needs to be open for over flow relief. Please do not close off with flashing.
SHEETS 1.2 AND 1.3
5. Provide balcony and patio wrought iron railing details.
SHEET 3.1
6. Please provide structural calculations for foundation F2, F4, F7, F10, F11, and F12 as per drawing footing schedule.
SHEET 5.2
7. Calculations call for B18 to be W12x14 minimum. Drawings show W8x21. Please reconcile.
8. Calculations call for B19 to be W12x14 minimum. Drawings show 8x18, 8x21, W16x26 and W12x22. Please reconcile.
SHEETS 9.3, 9.4, 9.5 AND 9.6
9. City of Tucsom minimum actual lettering size (not font identification) is 3/32" for both upper and lower case. Please revise sheets not in compliance with this standard and resubmit.
END OF REVIEW
08/23/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM04719
2221 N Rosemont Bl
New Two Story Elder Care Center

1. Provide 2012 IECC interior lighting code compliance calculations.
2. Indicate if power panels are to be fully rated including circuit breakers or series rated systems to be used.


Ray Majuta
Elect Plan Review
PDSD, C of Tucson,
8/26/2013

Final Status

Task End Date Reviewer's Name Type of Review Description
08/28/2013 CPIERCE1 REJECT SHELF Completed