Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T13CM04698
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/27/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
09/05/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
09/05/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Comment not resolved; Trane manufactures many different controls with various features. Show that each rooftop unit has a thermostatic control that provides for off-hour and set-back control, automatic shutdown and start-up control and, if the control does not require manual changeover from the heating and cooling modes, restricts set point overlap. [Initial comment: Verify that the controls for the new HVAC units (AC-23 and AC-24) have been provided with controls that comply with Section C403.2.4, IECC 2012.] |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/10/2013 | CPIERCE1 | REJECT SHELF | Completed |