Permit Number: T13CM04698
Parcel: 11016221A

Address:
6255 E GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T13CM04698
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/27/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
09/05/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
09/05/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not resolved; Trane manufactures many different controls with various features. Show that each rooftop unit has a thermostatic control that provides for off-hour and set-back control, automatic shutdown and start-up control and, if the control does not require manual changeover from the heating and cooling modes, restricts set point overlap. [Initial comment: Verify that the controls for the new HVAC units (AC-23 and AC-24) have been provided with controls that comply with Section C403.2.4, IECC 2012.]

Final Status

Task End Date Reviewer's Name Type of Review Description
09/10/2013 CPIERCE1 REJECT SHELF Completed