Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/31/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
07/31/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
08/01/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
08/12/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
08/12/2013 | RONALD BROWN | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
08/14/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T13cm04669 6025 E Broadway Best Buy T I 1. Unable to clearify Keyed Notes # 2 and 3. The plan appears to show a circuit connectio from the ceiling to display fixture on floor, Keyed note # 3 indicates to see detail 4/E8.0, there is no Sheet E8.0. However Sheet E4.0 detail 4 may be what is intended ? 2. Also is the circuit from an existing lighting circuit in the cieling brought down to feed a fixture at display level as shown on detail 6 Sheet E4.0. 3 Which circuits are being used and how will existing loads be effected ? 4. Provide circuits , panel and loads for Keyed Notes #6 and # 8 and show on plan. Ray T Majuta Elect Plan Review PDSD, Tucson 8/14/2013 Ray.Majuta@tucsonaz.gov |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
08/19/2013 | CPIERCE1 | REJECT SHELF | Completed |