Permit Number: T13CM04664
Parcel: 10512020C

Address:
4132 N ORACLE RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM04664
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/31/2013 STEVE SHIELDS ZONING REVIEW Approved
07/31/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
07/31/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
07/31/2013 ROBERT SHERRY WATER REVIEW Approved
07/31/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Needs Review 1. Cannnot access toilet through a backroom of a mercantile.
2. Occupancy load claculation is incorrect for mercantile. Use 1/30 and 1/300 as per Table 1004.1.2.
a. Reevaluate exit requitements for new occupancy load.
END OF REVIEW
07/31/2013 JASON GREEN ENGINEERING REVIEW Approved
07/31/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
07/31/2013 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/01/2013 KEN BROUILLETTE FIRE REVIEW Approved
08/07/2013 GERRY KOZIOL WWM REVIEW Approved