Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T13CM04643
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/30/2013 | ELIZABETH LEIBOLD | ENGINEERING | REVIEW | Approved | |
07/30/2013 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved | |
08/08/2013 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | Incomplete submittal package. No architectural, site, nor foundation plans for new structure. |
08/12/2013 | STEVE SHIELDS | ZONING | REVIEW | Denied | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: St. Mary's Generator Upgrade T13CM04643 Building Plan (1st Review) TRANSMITTAL DATE: August 13, 2013 1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. As this project proposed changes to the existing site and changes to a parking area that was approved under a temporary use permit (TUP), which has expired, a new development package is required. This development package can be accomplished by the following; Provide a copy of last approved site/development plan sheet that includes the vehicle parking calculation. Provide a copy of the last approved site/development plan with the area of change clouded. Provide a detail sheet similar to sheet E1.2 PH1, provided with this submittal, showing a fully dimensioned vehicle use area the meets the requirements of UDC Section 7.4.6. Provide revised vehicle parking calculations. 3. Zoning can not approve the building plans until a development package has been submitted and approved. 4. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
08/15/2013 | MARTIN BROWN | FIRE | REVIEW | Denied | Please provide specifications on the generators and the fuel tank to be installed. Indicate how compliance with the 2012 IFC section 604, NFPA 110 and NFPA 111 will be met. Is this building a high rise?KBROUILLETTE |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
08/22/2013 | SHANAE POWELL | OUT TO CUSTOMER | Completed |