Permit Number: T13CM04635
Parcel: 11105063J

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T13CM04635
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/30/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied Please provide structural calculations for all new HVAC suspended equip.
Provide structural engineer conformation that New roof top compressor load is ok for existing roof structure.
07/30/2013 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/30/2013 JASON GREEN ENGINEERING REVIEW Approved
07/30/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide information to show that the installation of A/C units meets the requirements of the 2012 IECC.
2. Revise the ventilation calculations per Section 403, IMC 2012.
07/30/2013 KEN BROUILLETTE FIRE REVIEW Approv-Cond storage over 12 feet is not allowed unless fire sprinkler system has been designed for high piled storage
07/30/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
07/30/2013 STEVE SHIELDS ZONING REVIEW Approved
08/01/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/01/2013 SHANAE POWELL OUT TO CUSTOMER Completed