Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T13CM04635
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/30/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | Please provide structural calculations for all new HVAC suspended equip. Provide structural engineer conformation that New roof top compressor load is ok for existing roof structure. |
| 07/30/2013 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 07/30/2013 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 07/30/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide information to show that the installation of A/C units meets the requirements of the 2012 IECC. 2. Revise the ventilation calculations per Section 403, IMC 2012. |
| 07/30/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approv-Cond | storage over 12 feet is not allowed unless fire sprinkler system has been designed for high piled storage |
| 07/30/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 07/30/2013 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 08/01/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/01/2013 | SHANAE POWELL | OUT TO CUSTOMER | Completed |