Permit Number: T13CM04512
Parcel: 120062080

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM04512
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/24/2013 MICHAEL ST. PAUL ZONING REVIEW Approved
07/24/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
07/24/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Passed
07/24/2013 ROBERT SHERRY WATER REVIEW Approved
07/24/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Passed
07/24/2013 LOREN MAKUS ENGINEERING REVIEW Approved
07/24/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the proposed size of the new water meter. The meter is called out as 2" on sheet P1 but on sheet P2 it is justified as a 1" meter.
2. Indirect waste piping that has a developed length greater than 30-inches (30") when measured horizontally or greater than 54-inches (54") in total developed length shall be trapped. Exception: indirect waste piping conveying only clear-water waste (e.g. effluent from a sanitizing compartment) does not require a trap. Reference: Section 802.2, IPC 2012.
3. Verify that all of the vents rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2012.
07/24/2013 MARTIN BROWN FIRE REVIEW Approved
07/24/2013 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/30/2013 FRODRIG2 WWM REVIEW Needs Review