Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM04512
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/24/2013 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 07/24/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 07/24/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
| 07/24/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/24/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Passed | |
| 07/24/2013 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 07/24/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Clarify the proposed size of the new water meter. The meter is called out as 2" on sheet P1 but on sheet P2 it is justified as a 1" meter. 2. Indirect waste piping that has a developed length greater than 30-inches (30") when measured horizontally or greater than 54-inches (54") in total developed length shall be trapped. Exception: indirect waste piping conveying only clear-water waste (e.g. effluent from a sanitizing compartment) does not require a trap. Reference: Section 802.2, IPC 2012. 3. Verify that all of the vents rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2012. |
| 07/24/2013 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 07/24/2013 | RONALD BROWN | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 07/30/2013 | FRODRIG2 | WWM | REVIEW | Needs Review |