Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T13CM04414
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/01/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Drawing MP2 appears to be a modification of the previously approved sheet M1. Clarify the extent of the changes to the previously approved drawing (e.g. clouds for the changes to the new ductwork, the existing AC-1 that is now the existing HP-2, etc). 2. Provide structural calculations for the installation of HP-1. |
| 04/01/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide specifications for fixture P-3 along with its valves. 2. Show the overflow for fixture P-3. |
| 04/03/2014 | SPOWELL1 | FIRE | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/03/2014 | SHANAE POWELL | OUT TO CUSTOMER | Completed |