Review Date Reviewer's Name Type of Review Description Status Comments
01/07/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Drawing MP2 appears to be a modification of the previously approved sheet M1. Clarify the extent of the changes to the previously approved drawing (e.g. clouds for the changes to the new ductwork, the existing AC-1 that is now the existing HP-2, etc).
2. Provide structural calculations for the installation of HP-1.
01/07/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide specifications for fixture P-3 along with its valves.
2. Show the overflow for fixture P-3.
3. Provide specifications for the piping materials to be used.
04/01/2014 SPOWELL1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/01/2014 SHANAE POWELL APPROVAL SHELF Completed
04/01/2014 SHANAE POWELL OUT TO CUSTOMER Completed