Permit Number - T13CM04400
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/22/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Verify that the mechanical plans for work areas B and C are correctly labeled on sheets MD.2, MD.4, M.2, and M.4. The plan labels appear to be reversed.
2. Verify the chilled water connections to fan coil FC-30.
07/22/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/30/2013 CPIERCE1 REJECT SHELF Completed