Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T13CM04332
Parcel: 13342001G

Address:
1925 N KOLB RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM04332
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/17/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Some of the proposed appliances (e.g. dishwasher, Concordia) require incoming water pressure in excess of the 15 PSI minimum flow pressure shown in the water calculations. Verify that the water distribution system can provide the flow pressure prescribed by the fixture or appliance manufacturer, which ever is greater. Reference: Section 604.3, IPC 2012, as amended by the City of Tucson.
2. Appliances (e.g. soda dispensers, ice makers, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2012.
3. An approved 2-way cleanout fitting is allowed to be used at the junction of a building drain and a building sewer; otherwise, cleanouts shall open to allow cleaning in the direction of flow. Reference: Sections 708.3.5 and 708.5, IPC 2012.
4. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012.
5. Verify that all of the vents (indoors) rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2012.
07/18/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Verify the termination point of the roof drains. Condensate drains may not terminate over a roof drain unless the roof drain itself terminates at or above grade in an area capable of absorbing the condensate flow without surface drainage. Reference: Section 307.2.1, IMC 2012, as amended by the City of Tucson.
2. Revise the structural calculations Type II hood to account for the actual hood weight and the weight of a person cleaning the hood. The structural drawings show a hood weight of 400 pounds and the specified hood has a weight of 315 pounds which will severely limit the size of the employees cleaning the hood. In addition, the shop drawings are proposing a hood that weighs 572 pounds. Reference: Section 507.6, IMC 2006.
08/01/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM04332
1925 N Kolb Rd

1. Sheet E610, Panel G ;
A phase shows 29,745 va divided by 120 v = 247.8 a
B Phase shows 31,194 va divided by 120 v = 259.9 a
2. Cannot locate circuit 35 Panel G ?


Ray T Majuta
DSD, Tucson,
Elect Plan Review
8/01/2013
Ray.Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
08/12/2013 CPIERCE1 REJECT SHELF Completed