Permit Number: T13CM04332
Parcel: 13342001G

Address:
1925 N KOLB RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM04332
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/17/2013 MICHAEL ST. PAUL ZONING REVIEW Approved
07/17/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Needs Review
07/17/2013 CPIERCE1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
07/17/2013 ROBERT SHERRY WATER REVIEW Approved
07/17/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. COVER: THE CITY OF TUCSON REQUIRES ALL LETTERING TO BE A MINIMUM OF 3/32" IN HEIGHT (UPPER AND LOWER CASE). REVISE THE INDEX.
2. COVER; APPLICABLE CODES: REMOVE THE REFERENCE TO THE 2010 ADA GUIDELINES. REVISE THE ICC/ANSI CODE REFERENCE TO THE 2009 EDITION.
3. STRUCTURAL CALCULATIONS; SHEET 4: THE CALCULATIONS INDICATE A NEW HOOD WEIGHT OF 400 POUNDS, WHILE THE MECHANICAL SHOP DRAWINGS INDICATE A HOOD WEIGHT OF 570+/- POUNDS. REVISE THE CALCULATIONS.
07/17/2013 CPIERCE1 WWM REVIEW Needs Review
07/17/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review
07/17/2013 LAITH ALSHAMI ENGINEERING REVIEW Approved
07/17/2013 MARTIN BROWN FIRE REVIEW Approved
07/17/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed