Permit Number: T13CM04216
Parcel: 10819224A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM04216
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/07/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Appliances (e.g. ice makers) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC 2012 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2012.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/08/2013 SHANAE POWELL OUT TO CUSTOMER Completed
08/08/2013 CPIERCE1 REJECT SHELF Completed