Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T13CM04213
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/11/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/12/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | The roof for this building does not have continuous insulation. Continuous insulation is uninterrupted by structural elements. The building section on sheet A3-F shows a screw-down metal roof without thermal blocks with insulation compressed between the roof deck and the purlins; R-13 is the maximum insulation that can be compressed with a screw-down metal roof. [Initial comment: Coordinate the R-value and type of insulation shown for the components in the envelope energy calculations with the components shown on the drawings. The roof appears to have insulation located in the roof cavity (continuous insulation is located above the roof deck) and the walls are shown with R-13 cavity insulation on the drawing but the calculations are based on R-19 cavity insulation in the walls.] |
| 09/12/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The civil drawing does not show the location or size of the reduced pressure backflow preventer assembly. Revise the civil drawing as required and include it in the building drawing set as a reference. [Initial comment: Provide a site drawing showing the size and route of the building water supply along with the location and size of both the water meter and the reduced pressure backflow preventer assembly. Reference: Section 107.2.1, IBC 2012.] 2. Revise the vents for both water closets; they run horizontally prior to rising above the flood rims of the water closets. [Initial comment: Verify that all of the vents rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2012.] |
| 09/12/2013 | ROBERT SHERRY | WATER | REVIEW | Denied | According to the records at Tucson Water, this address has a 5/8" water meter, not a ¾' meter. Contact Tucson Water for replacement of the existing 5/8" meter with a ¾" meter (contact: Scott Schladweiler @ 520-837-2122) [Initial comment: Water demand calculations based upon Appendix E, 2012 IPC show a total of 17.5 water fixture units and a demand of approximately 19 GPM for this building. Tucson Water limits the use of a 5/8" meter to 15 GPM. Provide a letter from Tucson Water confirming that the use of a 5/8" water meter will be allowed for this project.] |
| 09/18/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 09/19/2013 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/25/2013 | CPIERCE1 | REJECT SHELF | Completed |