Permit Review Detail
Review Status: Completed
Review Details: WALK THRU - COMM
Permit Number - T13CM04198
Review Name: WALK THRU - COMM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/17/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 07/17/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 07/18/2013 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | Original comment ' 3. Question- this permit is for Suite 110, the new service is marked Suite 109 ? Will Panel for Suite 110 not handle these circuits ?" unresolved. What is the purpose of adding a new service for suite 110 when the provided combined loads are less than than the 200A available at existing service? nec 230.2 2) the fault current calculations provided do not match the service installation shown. |