Permit Number: T13CM04198
Parcel: 10703138A

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T13CM04198
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/17/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
07/17/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
07/18/2013 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved Original comment ' 3. Question- this permit is for Suite 110, the new service is marked Suite 109 ? Will Panel for Suite 110 not handle these circuits ?" unresolved.

What is the purpose of adding a new service for suite 110 when the provided combined loads are less than than the 200A available at existing service? nec 230.2

2) the fault current calculations provided do not match the service installation shown.