Review Details: COMMERCIAL - TI

Permit Number - T13CM04198
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/10/2013 STEVE SHIELDS ZONING REVIEW Approved
07/10/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
07/10/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/11/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Verify that the proposed programmable thermostats for AC-1, FC-1, and FC-2 include the applicable control features detailed in Sections C403.2.4.1, C403.2.4.2, and C403.2.4.3, IECC 2012.
2. Provide automatic shutoff dampers for the outdoor air supply inlets (e.g. SF-1 and AC-1). Reference: SectionC403.2.4.4, IECC 2012.
07/11/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM04198

1. Provide some type of load for existing 1200 amp service.
2. Panel D circuits 9,11,13 marked space in schedule.
3. Question- this permit is for Suite 110, the new service is marked Suite 109 ? Will Panel for Suite 110 not handle these circuits ?
4. Fault current calculation for allowing new panel at 10K AIC.

Ray Majuta
Elect Pln Review
PDSD, Tucson
7/11/2013
07/11/2013 ROBERT SHERRY WATER REVIEW Approved
07/11/2013 MARTIN BROWN FIRE REVIEW Approved
07/11/2013 JASON GREEN ENGINEERING REVIEW Approved
07/11/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The term "wet vent" as shown in detail 3/P2.0 is not correct under the IPC because a urinal is not part of a bathroom group; you have shown a "common vent" installation with the pipe between the urinal and the lavatory considered an extension of the vertical drain. The presence of a 2" cleanout in the common vent above the two fixtures precludes the reduction of the vent beyond the cleanout to 1-1/2". Reference: Sections 202 912, IPC 2012
07/16/2013 GERRY KOZIOL WWM REVIEW Approved