Permit Number: T13CM04150
Parcel: 11007414D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM04150
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/14/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/14/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the structural calculations to reflect the way the hood is to be supported (the hood is not supported by the wall) and include the weight of a person working on the hood. [Initial comment: Provide structural calculations and details to show that the Type I hood is supported from the building structure in accordance with Section 507.6, IMC 2006. Reference: Section 302.1, IMC 2012.]
08/14/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
08/15/2013 SPOWELL1 PLUMBING-COMMERCIAL REVIEW Needs Review