Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM04150
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/14/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
08/14/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the structural calculations to reflect the way the hood is to be supported (the hood is not supported by the wall) and include the weight of a person working on the hood. [Initial comment: Provide structural calculations and details to show that the Type I hood is supported from the building structure in accordance with Section 507.6, IMC 2006. Reference: Section 302.1, IMC 2012.] |
08/14/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
08/15/2013 | SPOWELL1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review |