Permit Number: T13CM04149
Parcel: 11901042B

Address:
200 E BENSON HY

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM04149
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
01/06/2014 ROBERT SHERRY WATER REVIEW Approved
01/06/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show how the supports are connected to the building structure. [Initial comment: Provide details to show that the Type I hood is supported from the building structure in accordance with Section 507.6, IMC 2006 (Detail 3/M2.1 is missing). Reference: Section 302.1, IMC 2012.]
01/06/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide separate indirect waste pipes from each sink compartment. [Initial comment: Provide indirect waste pipes for each compartment of the 3-compartment sink. Provide separate indirect waste pipes to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012.]
02/07/2014 CPIERCE1 WWM REVIEW Completed