Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM04149
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/03/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/06/2014 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 01/06/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show how the supports are connected to the building structure. [Initial comment: Provide details to show that the Type I hood is supported from the building structure in accordance with Section 507.6, IMC 2006 (Detail 3/M2.1 is missing). Reference: Section 302.1, IMC 2012.] |
| 01/06/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide separate indirect waste pipes from each sink compartment. [Initial comment: Provide indirect waste pipes for each compartment of the 3-compartment sink. Provide separate indirect waste pipes to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012.] |
| 02/07/2014 | CPIERCE1 | WWM | REVIEW | Completed |