Permit Review Detail
Review Status: Completed
Review Details: REVISION - WALK THRU
Permit Number - T13CM04120
Review Name: REVISION - WALK THRU
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/27/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | Please explain the changes to the seating arrangement and weither or not the occupany has been changed from that as shown on the drawings. END OF REVIEW |
| 08/27/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/27/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide the listing information for the new pizza oven. |
| 08/27/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide a complete diagram of the natural gas distribution system showing the all of the loads, developed lengths, and the layout of the distribution piping to verify that the addition of the pizza oven will not result in any part of the natural gas piping system becoming overloaded. Reference: Section 107.2.1, IBC 2012. |