Permit Number: T13CM04120
Parcel: 13322500H

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T13CM04120
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/24/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Toilet room corridor is non-compliant with 2009 ICC A117.1, Section 404.2.3.2., 4'-0" wide
2. Provide door clearances as required by 2009 ICC A117.1, section 404.2.3.2 for doors 104a and 101b, show dimensions.
3. Show occupancy load breakdown by occupancy classification and provide a total summary. Show indoor count and outdoor count.
a. LIfe Safety Plan shows a total dining load of 212, Means of Egress analysis shows 129.1. Please reconcile.
b. Reaffirm toilet fixture count and required number of exits.
END OF REVIEW
07/24/2013 ROBERT SHERRY WATER REVIEW Approved
07/24/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the vents for the two floor sinks to eliminate the horizontal vents located below the flood rims of the sinks. [Initial comment: Verify that all horizontal branch vents, relief vents, or loop vents located indoors are located at least 6" above the flood rim of the highest fixture served. Reference: Section 905.5, IPC 2012.]
07/24/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Based on the information shown on the cut sheet for the pizza oven, a Type I hood rated for solid-fuel use and equipped with an approved fire suppression system is required. [Initial comment: Provide the cut sheets for the proposed wood-fired pizza oven.]
07/25/2013 LOREN MAKUS ENGINEERING REVIEW Approved
07/25/2013 TERRY STEVENS ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/02/2013 SHANAE POWELL OUT TO CUSTOMER Completed