Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T13CM04120
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/24/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Toilet room corridor is non-compliant with 2009 ICC A117.1, Section 404.2.3.2., 4'-0" wide 2. Provide door clearances as required by 2009 ICC A117.1, section 404.2.3.2 for doors 104a and 101b, show dimensions. 3. Show occupancy load breakdown by occupancy classification and provide a total summary. Show indoor count and outdoor count. a. LIfe Safety Plan shows a total dining load of 212, Means of Egress analysis shows 129.1. Please reconcile. b. Reaffirm toilet fixture count and required number of exits. END OF REVIEW |
| 07/24/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/24/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Revise the vents for the two floor sinks to eliminate the horizontal vents located below the flood rims of the sinks. [Initial comment: Verify that all horizontal branch vents, relief vents, or loop vents located indoors are located at least 6" above the flood rim of the highest fixture served. Reference: Section 905.5, IPC 2012.] |
| 07/24/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Based on the information shown on the cut sheet for the pizza oven, a Type I hood rated for solid-fuel use and equipped with an approved fire suppression system is required. [Initial comment: Provide the cut sheets for the proposed wood-fired pizza oven.] |
| 07/25/2013 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 07/25/2013 | TERRY STEVENS | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/02/2013 | SHANAE POWELL | OUT TO CUSTOMER | Completed |