Permit Number: T13CM04120
Parcel: 13322500H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM04120
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/08/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET t-1.0; PROJECT CODE COMPLIANCE: REVISE THE ICC/ANSI CODE TO THE 2009 EDITION.
2. SHEET t-1.0; PROJECT CODE COMPLIANCE: REMOVE THE 2010 ADA REFERENCE.
3. SHEET t-1.0; SHEET INDEX: THERE IS NO SHEET
A-1.2 IN THE SET, BUT THERE IS A SHEET d-1.0 (NOT INCLUDED IN THE SHEET INDEX). REVISE.
4. SHEET s-1.1; FOUNDATION PLAN: A DETAIL 1/s1.1 IS REFERENCED AT A NEW COLUMN. REVISE THE REFERENCE TO SHEET s-1.2.
5. SHEET s-1.2; ROOF FRAMING PLAN: A DETAIL 4/s-1.1 IS REFERENCED AT A NEW BEAM. REVISE THE REFERENCE TO SHEET s-1.2.
6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
07/08/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide the cut sheets for the proposd wood-fired pizza oven.
2. Where does detail 8/M-1.3 occur?
07/08/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
07/08/2013 ROBERT SHERRY WATER REVIEW Denied Provide the total demand served by the existing 2" water meter.
07/08/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/08/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review
07/09/2013 MARTIN BROWN FIRE REVIEW Approv-Cond Cut sheets for pizza oven (not included with first submittal) must confirm no Type I hood required.
07/10/2013 GBONILL1 WWM REVIEW Needs Review
07/10/2013 GBONILL1 ZONING REVIEW Needs Review
07/10/2013 GBONILL1 ENGINEERING REVIEW Denied