Permit Number: T13CM04060
Parcel: 12809001A

Review Status: Active

Review Details: COMMERCIAL - NEW

Permit Number - T13CM04060
Review Name: COMMERCIAL - NEW
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
07/03/2013 ANY FIRE REVIEW Active
07/03/2013 ANY PLUMBING-COMMERCIAL REVIEW Active
07/03/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13cm04060

1. Provide the existing load to panel A
2. Provide the new load on panel B
3. Size the conduit and conductors feeding new panel B
4. Show the location of panel A

Ray Majuta
Elect Plan Review
PDSD, Tuc
7/3/2013
520/837-4988
07/03/2013 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: 5042 E. Broadway Blvd - Office Addition
T13CM04060
Building Plan (1st Review)

TRANSMITTAL DATE: July 3, 2013

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning can not approve the building plans until the development package has been submitted and approved.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
07/03/2013 ANY BUILDING-COMMERCIAL REVIEW Active
07/03/2013 ANY WATER REVIEW Active
07/03/2013 ANY MECHANICAL-COMMERCIAL REVIEW Active
07/03/2013 ANY ENGINEERING REVIEW Active
07/03/2013 ANY COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Active