Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM04033
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/19/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Eliminate the underground horizontal vents located indoors (e.g. P7 floor sinks), the vents may not be horizontal unless they are located at least 6" above the flood rim of the highest fixture served. Reference: Section 905.5, IPC 2012. |
07/19/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/22/2013 | AROMERO4 | APPROVAL SHELF | Completed |
07/22/2013 | AROMERO4 | OUT TO CUSTOMER | Completed |
07/22/2013 | AROMERO4 | REJECT SHELF | Completed |