Permit Number: T13CM04033
Parcel: 13602002L

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM04033
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/16/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Coordinate the plumbing design with the revised architectural floor plan.
2. The architectural floor plan shows an ice maker and a soda fountain but the plumbing plans do not show any water service to these appliances. If there is to be water service to these items, indicate the type of backflow protection required. In addition, indicate if any indirect waste receptors are required.
3. Provide structural calculations for the mounting shelf for the water heater to show that the water heater will be safely supported from the building structure. Reference: Section 301.2, IPC 2012.
4. If the water supply to the water heater is connected to the side inlet of the storage tank, provide a vacuum relief valve. Reference: Section 504.2, IPC 2012.
5. Redirect the lasso for keynote 18 on the water piping plan - it calls out the size of the gas pipe but is connected to the hot water pipe.
6. Clarify the size of the gas pipe on key note 16 on the water piping plan.
7. Revise the size of the water heater vent: the specified water heater has a 5" draft hood. Reference: Section 503.5.5 (2), IFGC 2012.
8. Show that the installation of the water heater will comply with the manufacturer's required clearance to combustibles (12" from the top). Verify that the minimum height of the flue termination is 5'- 0" above the draft hood. Reference: Sections 301.3 and 503.6.5, IFGC 2012.
07/16/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Coordinate the mechanical design with the revised architectural floor plan.
2. The architectural floor plan notes the presence of a "dishwasher w/ exhaust"; coordinate any exhaust requirements with the architect. Reference: Section 507.2.2, IMC 2012.
3. Provide structural calculations and details to show that the Type I hood is supported from the building structure in accordance with Section 507.6, IMC 2006. Reference: Section 302.1, IMC 2012.
4. Provide exhaust for the new restroom at the north wall of the suite. Reference: Section 403.3, IMC 2012.
5. Show that the hood installation complies with Section 507.9, IMC 2012 for clearances (i.e. provide information regarding the wall construction). The clearance reduction method shown in detail 3/M3 is not included in Table 308.6, IMC 2012 and must be accompanied with listing information to be considered.
07/16/2013 ROBERT SHERRY WATER REVIEW Approved
07/18/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved