Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM04033
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/03/2013 | TERRY STEVENS | ZONING | REVIEW | Passed | |
| 07/03/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 07/03/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 07/03/2013 | ROBERT SHERRY | WATER | REVIEW | Needs Review | |
| 07/03/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A1; FLOOR PLAN: THE EXISTING TOILET AND JANITOR CLOSET CAN NOT OPEN INTO A FOOD PREPARATION AREA. REVISE. |
| 07/03/2013 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 07/03/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 07/03/2013 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 07/03/2013 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 07/08/2013 | FRODRIG2 | WWM | REVIEW | Needs Review |