Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM03985
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/18/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
07/18/2013 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | RESPONSE TO ORIGINAL CORRECTION REQUEST INSUFFCIENT "Provide the Fault Current available at panel A, if AIC over 10K AIC indicate if panel to have a Series Rated System or Fully Rated System." IT IS UNCLEAR HOW THE FAULT CURRENT AT F6 WAS ARRIVED AT (ONE LINES DO NOT MATCH CALCULATION POINTS) AND NOTED FAULT CURRENT IS OVER 10K AIC WHILE PANEL BRACING HAS NOT BEEN INDICATED. 2) ORIGINAL CORRECTION REQUEST INCOMPLETE "Provide the total load on the 1200 amp service including this space". NO LOADS FOR OTHER THAN THIS SPACE HAVE BEEN PROVIDED. |