Permit Number: T13CM03985
Parcel: 110113620

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM03985
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/18/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
07/18/2013 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Reqs Change RESPONSE TO ORIGINAL CORRECTION REQUEST INSUFFCIENT "Provide the Fault Current available at panel A, if AIC over 10K AIC indicate if panel to have a Series Rated System or Fully Rated System." IT IS UNCLEAR HOW THE FAULT CURRENT AT F6 WAS ARRIVED AT (ONE LINES DO NOT MATCH CALCULATION POINTS) AND NOTED FAULT CURRENT IS OVER 10K AIC WHILE PANEL BRACING HAS NOT BEEN INDICATED.

2) ORIGINAL CORRECTION REQUEST INCOMPLETE "Provide the total load on the 1200 amp service including this space". NO LOADS FOR OTHER THAN THIS SPACE HAVE BEEN PROVIDED.