Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM03985
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/01/2013 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 07/01/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 07/01/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T13cm03985 1. Provide the Fault Current available at panel A, if AIC over 10K AIC indicate if panel to have a Series Rated System or Fully Rated System. 2. Provide the total load on the 1200 amp service including this space. Ray T Majuta PDSD, Tucson Elect Plan Review 7/1/2013 Ray.Majuta@tucsonaz.gov |
| 07/01/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/01/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A400; DETAILS 13 AND 17: STORAGE RACKS REQUIRE A SEPARATE PERMIT. SINCE THE RACKS ARE OVER 6' IN HEIGHT, PROVIDE A DETAIL OF HOW THE RACKS ARE CONNECTED TO THE FLOOR, INCLUDING CONNECTOR SIZE AND QUANTITY. 2. SHEET A510; DETAIL 10: PROVIDE A VERTICAL GRAB BAR PER FIGURE 604.5.1 OF THE ICC/ANSI. 3. SHEET A610; WALL A2: AT THE TOP OF THE WALL, INDICATE HOW THE BRACES ARE CONNECTED TO THE WALL AND TO THE STRUCTURE ABOVE (ADD SPECIFIC DETAILS), INCLUDING CONNECTOR SIZE AND QUANTITY. 4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 07/01/2013 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 07/01/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 07/01/2013 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 07/02/2013 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 07/18/2013 | SPOWELL1 | WWM | REVIEW | Needs Review |