Permit Number: T13CM03985
Parcel: 110113620

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM03985
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/01/2013 STEVE SHIELDS ZONING REVIEW Approved
07/01/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
07/01/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13cm03985

1. Provide the Fault Current available at panel A, if AIC over 10K AIC indicate if panel to have a Series Rated System or Fully Rated System.
2. Provide the total load on the 1200 amp service including this space.


Ray T Majuta
PDSD, Tucson
Elect Plan Review
7/1/2013
Ray.Majuta@tucsonaz.gov
07/01/2013 ROBERT SHERRY WATER REVIEW Approved
07/01/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A400; DETAILS 13 AND 17: STORAGE RACKS REQUIRE A SEPARATE PERMIT. SINCE THE RACKS ARE OVER 6' IN HEIGHT, PROVIDE A DETAIL OF HOW THE RACKS ARE CONNECTED TO THE FLOOR, INCLUDING CONNECTOR SIZE AND QUANTITY.
2. SHEET A510; DETAIL 10: PROVIDE A VERTICAL GRAB BAR PER FIGURE 604.5.1 OF THE ICC/ANSI.
3. SHEET A610; WALL A2: AT THE TOP OF THE WALL, INDICATE HOW THE BRACES ARE CONNECTED TO THE WALL AND TO THE STRUCTURE ABOVE (ADD SPECIFIC DETAILS), INCLUDING CONNECTOR SIZE AND QUANTITY.
4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
07/01/2013 LOREN MAKUS ENGINEERING REVIEW Approved
07/01/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
07/01/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/02/2013 MARTIN BROWN FIRE REVIEW Approved
07/18/2013 SPOWELL1 WWM REVIEW Needs Review