Permit Number: T13CM03778
Parcel: 13804180C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM03778
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/21/2013 STEVE SHIELDS ZONING REVIEW Approved
06/21/2013 LOREN MAKUS ENGINEERING REVIEW Approved
06/24/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied See comments on work flow sheet, plans required to be sealed by registrant.
1.Show one line diagram of service and existing loads plus new this space,show location of service.
2. Provide a spec sheet on Foot Spa in order to verify loads in panel.
3. Circuit 29 has a load in panel not shown in power plan.
4. Have registrant review all electrical and seal electrical
plans.

Ray Majuta
PDSD, Tucson
Elect Plan Review
6/24/2013
520-837-4988
06/25/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
06/25/2013 KEN BROUILLETTE FIRE REVIEW Denied Please update plans to the current adopted codes. Remove all notes that do not apply to this project.
06/25/2013 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/26/2013 FRODRIG2 MECHANICAL-COMMERCIAL REVIEW Needs Review
06/26/2013 FRODRIG2 PLUMBING-COMMERCIAL REVIEW Needs Review
06/26/2013 FRODRIG2 WATER REVIEW Needs Review
06/26/2013 FRODRIG2 WWM REVIEW Needs Review