Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM03778
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/21/2013 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 06/21/2013 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 06/24/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | See comments on work flow sheet, plans required to be sealed by registrant. 1.Show one line diagram of service and existing loads plus new this space,show location of service. 2. Provide a spec sheet on Foot Spa in order to verify loads in panel. 3. Circuit 29 has a load in panel not shown in power plan. 4. Have registrant review all electrical and seal electrical plans. Ray Majuta PDSD, Tucson Elect Plan Review 6/24/2013 520-837-4988 |
| 06/25/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/25/2013 | KEN BROUILLETTE | FIRE | REVIEW | Denied | Please update plans to the current adopted codes. Remove all notes that do not apply to this project. |
| 06/25/2013 | RONALD BROWN | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 06/26/2013 | FRODRIG2 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 06/26/2013 | FRODRIG2 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 06/26/2013 | FRODRIG2 | WATER | REVIEW | Needs Review | |
| 06/26/2013 | FRODRIG2 | WWM | REVIEW | Needs Review |