Permit Number: T13CM03769
Parcel: 121113250

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM03769
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/21/2013 MICHAEL ST. PAUL ZONING REVIEW Approved
06/21/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
06/21/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13cm03769
4805 E Speedway Bl

1. Cover sheet indicates 2008 NEC,we are under the 2011 NEC, change to 2011.
2. Provide a 2012 IECC Lighting Compliance Report, ComCheck ok.
3.Sheet E3.1 indicates the Fault Current Calculation for Panel A is 47,836 AIC, the panel schedule indicates 22,000.
The panel needs to be at better than 47,836. Indicate if a Series Rated or Fully Rated System to be used.

Ray Majuta
Elect Plan Review
PDSD, Tucson
6/21/2013
Ray.Majuta@tucsonaz.gov
06/21/2013 ROBERT SHERRY WATER REVIEW Approved
06/21/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Minimum actual (not font) lettering size is 3/32" for both upper and lower case.
2. Please provide a site plan.
3. Cannot access toilet rooms through storage rooms.
4. Correct accessibility code reference to 2009 Edition ICC A117.1.
5. Provide accessible water dispenser/s.
6. Do not show required exit from reception to storage room.
All exiting through door D-2.
7. Provide structural calculations for platform mounted water heater.
8. Remove accessible door signage from middle of door, wall mounted on the strike side of the door as per ICC A117.1.
END OF REVIEW
06/21/2013 JASON GREEN ENGINEERING REVIEW Approved
06/21/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
06/21/2013 MARTIN BROWN FIRE REVIEW Approved
06/21/2013 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/03/2013 GERRY KOZIOL WWM REVIEW Approved