Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM03746
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/25/2013 | KEN BROUILLETTE | FIRE | REVIEW | Denied | PLEASE PROVIDE OCCUPANT LOAD CALCULATIONS FOR MEZZ. AND FIRST FLOOR AND SHOW EXITING COMPLIANCE |
06/26/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | GENERAL 1. Please provide structural details and calculations for all new roof top mounted HVAC equipment and any suspended fan coil units. SHEET A1.0 2. Please provide a site plan. 3. Please complete the occupant load calculations as per 2012 IBC, Section 1004. SHEET A2.0 4. Please identify and show the accessible drinking fountain in room 135 Rehab. 5. The east partition of Room 124 Cardio is drawn as though it may be a 6" stud partition. The detail section reference 4/A6.3 calls for 3 5/8" studs. Please reconcile. SHEET A2.1 6. The second level designated as a Mezzanine does not meet the 2012 IBC requirements for a mezzanine, Section 505.2.3 and must therefore be considered a second story. a. As per exception 1, the occupant load can not be greater than 10. Your mezzanine load is somewhere near 68 occupants. b. As per exception 2, because you have more than 29 occupants, two exits are required and one must have direct access to an exit from the mezzanine which there is none. Please reference the 2012 IBC, Sections 1021, 1022 and 707. Please show your code analysis for the second floor determination. c. As per exception 3, your enclosed space can not be more than 10% which the actual enclosed space is somewhere near 20% or so. d. Please include an occupancy load calculation showing separately the first and second level occupant loads. 7. Please detail what the top of the exam rooms and toilet rooms to show what it will look like in plan. 8. Call out guard rail at the second floor ledge. SHEET A5.0 9. At detail 4, the room label Rehab 135 is incorrect. Please reconcile. 10. At detail 6: a. Delete all references to the 2010 ADAAG and replace with 2009 ICC A117.1. b. Please provide a vertical grab bar as required by 2009 ICC A117.1, Section 604.5.1. 11. Dimension the heights of the accessible drinking fountain spout heights as per 2009 ICC A117.1, Section 602.5. SHEET A6.0 12. At detail 1, relocate the sprinkler stand pipe as it reduces the required width of the stair landing as per Section 1009.4. SHEET A6.1 13. The guard rail shown here is not a pony wall, it is a guard rail. 14. Provide the minimum height dimension for the guard rail as per Section 1013.3. END OF REVIEW |
06/28/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
06/28/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2012, for business occupancy (e.g. drinking fountain). 2. Verify the static lift used for the water distribution system design; the highest fixtures are located on the mezzanine, approximately eighteen feet above the first floor elevation. Reference: Section 604.1, IPC 2012. |
07/01/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. The portion of the building shell being modified in this activity does not appear to have been previously conditioned. Section C101.4.5, IECC 2012 requires the space to be brought into full compliance with the energy code. Provide energy code compliance calculations for the building envelope; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections C103.2 and C401.2, International Energy Conservation Code 2012. 2. Show that the proposed HVAC system meets the requirements of Sections C403.2, C403.3 and, if neither the efficient lighting system nor the on-site renewable energy options are selected, C406.2, IECC 2012 (e.g. provide the mechanical energy code compliance certification from COMcheck). Reference: Section C303.1, International Energy Conservation Code 2012. 3. Provide signage indicating the total equivalent length of the concealed dryer exhaust duct. Reference: Section 504.6.5, IMC 2012. |
07/02/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
08/02/2013 | AROMERO4 | APPROVAL SHELF | Completed |
08/02/2013 | AROMERO4 | OUT TO CUSTOMER | Completed |
08/02/2013 | GERARDO BONILLA | REJECT SHELF | Completed |