Review Date Reviewer's Name Type of Review Description Status Comments
06/20/2013 MICHAEL ST. PAUL ZONING REVIEW Approved
06/20/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the sequence of operation for the restroom exhaust fans so that the fans run whenever HVAC air is supplied to the restrooms.
2. Revise the ventilation calculations by using the method shown in Section 403.3, IMC 2012.
06/20/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM03744
2941 N Swan RD

1. Minimun text on plans required to be 3/32'', per City of Tucson Submittal Requirements 2012.
2. Power sheet indicated circuit P1-1.3 used twice, one is for circuits P1-8,10,12.
3. The fault current calculations indicate Panel P1 to be
19,707 AIC and only 10,000 AIC rated. Correct the panel rating and indicate if a Series Rated System or Fully Rated System to be used on this panel. Per 2011 NEC 110.10.

Ray Majuta
Elect Plan Review
PDSD, Tucson
6/20/2013
Ray.Majuta@tucsonaz.gov
06/20/2013 ROBERT SHERRY WATER REVIEW Approved
06/20/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/20/2013 LAITH ALSHAMI ENGINEERING REVIEW Approved
06/20/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide an ASSE 1070 listed mixing valve for the lavatories.
06/20/2013 MARTIN BROWN FIRE REVIEW Approved
06/20/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/29/2013 CPIERCE1 WWM REVIEW Passed