Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/20/2013 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
06/20/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the sequence of operation for the restroom exhaust fans so that the fans run whenever HVAC air is supplied to the restrooms. 2. Revise the ventilation calculations by using the method shown in Section 403.3, IMC 2012. |
06/20/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T13CM03744 2941 N Swan RD 1. Minimun text on plans required to be 3/32'', per City of Tucson Submittal Requirements 2012. 2. Power sheet indicated circuit P1-1.3 used twice, one is for circuits P1-8,10,12. 3. The fault current calculations indicate Panel P1 to be 19,707 AIC and only 10,000 AIC rated. Correct the panel rating and indicate if a Series Rated System or Fully Rated System to be used on this panel. Per 2011 NEC 110.10. Ray Majuta Elect Plan Review PDSD, Tucson 6/20/2013 Ray.Majuta@tucsonaz.gov |
06/20/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
06/20/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
06/20/2013 | LAITH ALSHAMI | ENGINEERING | REVIEW | Approved | |
06/20/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide an ASSE 1070 listed mixing valve for the lavatories. |
06/20/2013 | MARTIN BROWN | FIRE | REVIEW | Approved | |
06/20/2013 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
08/29/2013 | CPIERCE1 | WWM | REVIEW | Passed |