Permit Number: T13CM03743
Parcel: 13502134K

Address:
7050 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM03743
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/24/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
06/26/2013 ROBERT SHERRY WATER REVIEW Approved
06/26/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
06/26/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied SHEET S0.1
1. Provide certification of the special inspectoras required as per the specifications.
SHEET A1.1.0
2. Provide a high low water dispenser as per the 2012 IBC, Section 1109.5, Table 2902.1 and the 2009 ICC A117.1, Section 602.
END OF REVIEW
06/27/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the sequence of operation for the restroom exhaust fans, EF-1 and EF-2, so that all of the air supplied to the restrooms will be exhausted. No more than 10% of the exhausted air from the restrooms may subsequently be recirculated. Reference: Section 403.2.1 (4), IMC 2012.
06/28/2013 MARTIN BROWN FIRE REVIEW Approved