Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM03743
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/24/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
06/26/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
06/26/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
06/26/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | SHEET S0.1 1. Provide certification of the special inspectoras required as per the specifications. SHEET A1.1.0 2. Provide a high low water dispenser as per the 2012 IBC, Section 1109.5, Table 2902.1 and the 2009 ICC A117.1, Section 602. END OF REVIEW |
06/27/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the sequence of operation for the restroom exhaust fans, EF-1 and EF-2, so that all of the air supplied to the restrooms will be exhausted. No more than 10% of the exhausted air from the restrooms may subsequently be recirculated. Reference: Section 403.2.1 (4), IMC 2012. |
06/28/2013 | MARTIN BROWN | FIRE | REVIEW | Approved |