Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM03631
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/14/2013 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 06/14/2013 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 06/14/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/14/2013 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 06/17/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 06/17/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T13CM03631 1. Provide a panel schedule describing the voltage,amperage,existing and new loads,total loads, location and indicate which circuit feed which equipment. This information is requested by City of Tucson Commercial Submittal for TI's. Ray Majuta Elect Plan Review PDSD, Tucson 6/17/2013 Ray.Majuta@tucsonaz.gov |
| 06/17/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/17/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 06/17/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide a design for the plumbing revisions. |
| 07/18/2013 | SPOWELL1 | WWM | REVIEW | Needs Review |