Permit Number - T13CM03582
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/12/2013 | STEVE SHIELDS | ZONING | REVIEW | Approved | Non Charter financial requires special exception prior to approval of TI |
| 06/12/2013 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 06/12/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET TS1: PROVIDE THE OCCUPANCY LOAD. 2. SHEET TS1; APPLICABLE CODES: INDICATE THE ICC/ANSI A117.1-2009 FOR THE ACCESSIBILITY CODE. 3. SHEET A4.0: REMOVED ALL REFERENCES TO ADA AND SUBSTITUTE ICC/ANSI FOR ACCESSIBILITY. 4. SHEET A4.0; RESTROOM GENERAL NOTES: NOTES 6 AND 7 REFERENCE THE 2010 ADA. REVISE. 5. SHEET A6.0; SECTION 8: CALL OUT THE BRACE SPACING AND CONNECTION TO THE TOP OF THE WALL AND TO THE STRUCTURE ABOVE. 6. SHEET A6.0; WALL SECTION KEY PLAN: WALL 11 WAS NOT LOCATED ON THE PLAN. VERIFY. 7. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 06/12/2013 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 06/13/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show that the proposed HVAC system meets the control requirements of Sections C403.2.4 and C403.3. Reference: Section C303.1, International Energy Conservation Code 2012. |
| 06/13/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/13/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/13/2013 | KEN BROUILLETTE | FIRE | REVIEW | Denied | PROVIDE OCCUPANT LOAD PLEASE |
| 06/13/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 06/17/2013 | CPIERCE1 | WWM | REVIEW | Needs Review |