Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T13CM03526
Parcel: 12709011M

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM03526
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/11/2013 TERRY STEVENS ZONING REVIEW Approved
06/11/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/11/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
06/11/2013 ROBERT SHERRY WATER REVIEW Approved
06/11/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
06/11/2013 CPIERCE1 WWM REVIEW Passed
06/11/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
06/11/2013 LOREN MAKUS ENGINEERING REVIEW Approved
06/11/2013 CARL SCHULTZ FIRE REVIEW Approved
06/11/2013 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
06/11/2013 CPIERCE1 OUT TO CUSTOMER Completed
06/11/2013 CPIERCE1 APPROVAL SHELF Completed